The ELETRAS three-phase motor starting reactor is designed to effectively limit inrush current during the startup of asynchronous motors and pumps. Connected in series with the motor, it reduces supply voltage to the stator at startup, ensuring smooth acceleration and protecting the system from electrical and mechanical stress. Ideal for industrial plants with frequent startups, it improves system reliability and extends component lifespan.
The ELETRAS three-phase motor starting reactor leverages inductive impedance to reduce the voltage supplied to the motor during startup, thereby lowering the typically high inrush current of asynchronous motors. This process mitigates current peaks and impulsive torques, ensuring smoother startups, reduced component wear, and greater plant stability.
The ELETRAS three-phase motor starting reactor is widely used in various industrial contexts, including:
Three-phase asynchronous motors: limits inrush current to protect windings and cables
Pumps and compressors: reduces torque and pressure fluctuations during startup
Plants with long motor cables: attenuates capacitive currents and improves efficiency
HVAC systems and machine tools: controlled startups and inverter protection
ELETRAS three-phase motor starting reactors comply with major European and international safety and quality standards:
EN 61558-2-20: safety requirements for industrial reactors
CEI EN 60076-6: standard for three-phase reactors and transformers
CE Marking: ensures compliance with European directives
These certifications guarantee safe, reliable performance fully in line with industry standards.
The ELETRAS three-phase motor starting reactor provides numerous operational benefits:
Effective inrush current limitation: protects both motor and line
Smooth startups: reduces vibrations and impulsive torques
Extended motor and system life: minimizes mechanical and electrical stress
Reduced maintenance costs: less wear on components
Easy integration: compact design for installation in existing panels
ELETRAS designs motor starting reactors tailored to the specific needs of each plant:
Dedicated nominal currents: selectable based on motor power
Custom connections: terminals or clamps for easier wiring
Additional protection: plexiglass shields and covers available
Special configurations: suitable for harsh environments or specific requirements
Customizable number and duration of starts/hour: for heavy-duty operating cycles
Number of switchings: adaptable to specific switching frequencies
Each supply is developed in collaboration with the customer to ensure maximum reliability and performance.
POWER: Asynchronous motors from 5 to 300HP
CUSTOMIZABLE FEATURES:
Quantity of startings
Quantity of insertions
Plexiglass protection for connectors
TECHNICAL DATA:
Continuous service
Frequency: 50/60Hz
Protection degree: IP00
Thermal isolation class: B(130°C)/F(155°C)
Power: 400V
STANDARD PRODUCT FOR STARTING OF ASYNCHRONOUS MOTORS (3 startings/h, duration 5 seconds):
|
Code
|
Power (HP)
|
Lenght (A)
|
Depth (B)
|
Height (H)
|
Connection
|
|
REA5A
|
5 | 180 | 130 | 130 | TERMINALS / BAKELITE BOARD WITH BRASS SCREWS |
| REA7,5A | 7,5 | 180 | 130 | 130 | TERMINALS / BAKELITE BOARD WITH BRASS SCREWS |
| REA10A | 10 | 180 | 140 | 140 | TERMINALS / BAKELITE BOARD WITH BRASS SCREWS |
| REA15A | 15 | 180 | 150 | 150 | TERMINALS / BAKELITE BOARD WITH BRASS SCREWS |
| REA20A | 20 | 180 | 160 | 160 | TERMINALS / BAKELITE BOARD WITH BRASS SCREWS |
| REA25A | 25 | 240 | 175 | 175 | TERMINALS / BAKELITE BOARD WITH BRASS SCREWS |
| REA30A | 30 | 240 | 185 | 185 | TERMINALS / BAKELITE BOARD WITH BRASS SCREWS |
| REA40A | 40 | 240 | 200 | 200 | TERMINALS / BAKELITE BOARD WITH BRASS SCREWS |
| REA50A | 50 | 300 | 180 | 180 | TERMINALS / BAKELITE BOARD WITH BRASS SCREWS |
| REA60A | 60 | 300 | 190 | 190 | TERMINALS / BAKELITE BOARD WITH BRASS SCREWS |
| REA75A | 75 | 300 | 190 | 190 | TERMINALS / BAKELITE BOARD WITH BRASS SCREWS |
| REA100A | 100 | 300 | 200 | 200 | TERMINALS / BAKELITE BOARD WITH BRASS SCREWS |
| REA125A | 125 | 300 | 210 | 210 | TERMINALS / BAKELITE BOARD WITH BRASS SCREWS |
| REA150A | 150 | 360 | 240 | 240 | TERMINALS / BAKELITE BOARD WITH BRASS SCREWS |
| REA175A | 175 | 360 | 250 | 250 | TERMINALS / BAKELITE BOARD WITH BRASS SCREWS |
| REA200A | 200 | 360 | 260 | 260 | TERMINALS / BAKELITE BOARD WITH BRASS SCREWS |
| REA300A | 300 | 420 | 300 | 300 | TERMINALS / BAKELITE BOARD WITH BRASS SCREWS |
STANDARD PRODUCT FOR STARTING OF PUMPS (4 startings/h, duration 20 seconds):
|
Code
|
Power (HP)
|
Length (A)
|
Depth (B)
|
Height (H)
|
Connection
|
| REA10B | 10 | 150 | 80 | 155 | TERMINALS / BAKELITE BOARD WITH BRASS SCREWS |
| REA15B | 15 | 150 | 90 | 155 | TERMINALS / BAKELITE BOARD WITH BRASS SCREWS |
| REA20B | 20 | 150 | 90 | 155 | TERMINALS / BAKELITE BOARD WITH BRASS SCREWS |
| REA25B | 25 | 180 | 95 | 185 | TERMINALS / BAKELITE BOARD WITH BRASS SCREWS |
| REA30B | 30 | 180 | 95 | 185 | TERMINALS / BAKELITE BOARD WITH BRASS SCREWS |
| REA40B | 40 | 180 | 105 | 185 | TERMINALS / BAKELITE BOARD WITH BRASS SCREWS |
| REA50B | 50 | 180 | 115 | 185 | TERMINALS / BAKELITE BOARD WITH BRASS SCREWS |
| REA60B | 60 | 240 | 125 | 240 | TERMINALS / BAKELITE BOARD WITH BRASS SCREWS |
| REA70B | 70 | 240 | 135 | 240 | TERMINALS / BAKELITE BOARD WITH BRASS SCREWS |
| REA100B | 100 | 240 | 145 | 250 | TERMINALS / BAKELITE BOARD WITH BRASS SCREWS |
| REA150B | 150 | 300 | 200 | 260 | TERMINALS / BAKELITE BOARD WITH BRASS SCREWS |
| REA200B | 200 | 300 | 200 | 260 | TERMINALS / BAKELITE BOARD WITH BRASS SCREWS |